8

SPECIFICATIONS

VH Series

: 700

1000

1500

2000

Ratings

Voltage Amperes (VA) with computer type load

: 700

1000

1500

1920

Watts (W) with resistive load

: 630

900

1350

1740

Input thermal circuit breaker (A)

: 8

12

18

20

Internal input fuse 250V, slow (A)

: 15

15

30

30

Input converter

AC input voltage

: 60 - 140 V

Input current waveform

: sinusoidal, EN 61000-3-2 (IEC 555-2) compliant

Input current (A) at nominal input voltage

: 6.6

9.1

13.9

16

Input power factor

: 1

Input frequency range

: 45 - 66 Hz

Inrush current

: none

Output converter

AC output voltage

: 100 / 110 / 115/120/127 V (selectable)

AC output voltage tolerance

: ± 2%

Output frequency

: auto selectable or 50 / 60 Hz, front selectable

Output frequency range

: nominal ± 0.05%

Output waveform

: sine wave

Harmonic distortion

: < 1% with linear load

Power factor

: 0.9

Crest factor (peak to RMS current)

: suitable for loads with c.f. up to 3:1

Capacity appliance outlets

: max. 20A per outlet (+ 1 high power outlet max. 20A, on 2000VA model only)

Bypass

AC input voltage range

: selected output voltage -15% to +10%

Frequency tracking rate

: 2 Hz/sec.

Frequency tracking range

: nominal ± 10% / ± 2% selectable

Phase difference

: < 1º typical (max. 7º during tracking frequency range)

Typical transfer time, msec

: 1

Overload capability

: fully protected against overload and short circuits

Overload behaviour during battery operation

: 110% 4 minutes

: 150% 2 seconds

Overload behavior during bypass operation

: depends on rating of thermal circuit breaker

typical: 125% of TCB value for 200 seconds

200% of TCB value for 10 seconds

300% of TCB value for 4 seconds

Batteries (ratings given for 77ºF

Nominal voltage (Vdc)

: 36

36

72

72

Number / Ah batteries

: 3/7

3/9

6/7

6/9

Type

: sealed lead acid, maintenance free

Service life

: up to 6 years (depending on use)

Recharge current

: 1.5 A

Battery recharge time

(batt. discharged at 100% load)

: 3 hours for 90% capacity, std battery

Runtime in minutes at typical load (75%)

: 12

12

11

12

VA/Watts

250/225

: 22

35

58

70

500/450

: 12

18

28

36

700/630

: 8

12

21

27

1000/900

:

8

13

20

1500/1350

:

7

12

1920/1740

:

8

General

Weight UPS (lbs/kg)

: 35/16

37/17

64/29

71/32

Dimensions UPS (HxWxD)

:

3.4x17.2x18.5inch

3.4x17.2x21.3 inch

:

87x438x470 mm

87x438x540 mm

Enclosure / protection

: steel-plastic / IP20

Battery pack

Nominal Voltage (Vdc)

:

36

72

Nominal Capacity (Ah)

: 14

Weight (lbs/kg)

:

60/27

101/46

Dimensions (HxWxD)

:

3.4x17.2x18.5inch

3.4x17.2x21.3 inch

:

87x438x470 mm

87x438x540 mm

Environment

Safety

: UL 1778, 4

th

Edition

Electromagnetic compatibility

: EN 62040-2

Ambient temperature

: 32 to 104ºF (0 to +40ºC)

Audible noise at 1 meter

: < 45 dB(A), load and temperature dependent

Max. relative humidity

: 95% (non-condensing)