Alarm Reference Table

This Alarm Table shows how FTTN Alarms are categorized by the QS941 Controller. Many alarms are
best processed at the converter shelf alarm card and converter card level. In other words columns 4, and
5, can be used to select the appropriate action from column 6.

[QS941 Controller Page 27]

3.

QS941

4.

Alarm Card

5.

Converter Card

6.

Human Response

1.

Alarm
Display

2.

What it

means

LED

State

Relay

State

Alarm

LED

State

Relay

State

OK

LED

State

Alarm

LED

State

Corrective Action

Circuit Fail

Short + to -

Yellow

Min Yellow Min Green Flashing

Yellow

Make sure each converter

has an independent isolated
send and return path.

Circuit Fail

Short to

Ground

Yellow

Min Yellow Min Flashing

Red

Flashing

Red

Make sure each converter

has an independent isolated
send and return path.

Comm. Fail

1 Card

Removed

Yellow

Min

Yellow

Min

Green

Off

Check to see that all cards

are seated. Replace non-
functioning cards.

Comm. Fail

2 Cards
Removed

Red

Maj

Check to see that all cards
are seated. Replace non-
functioning cards.

Comm. Fail

Comm.
Cable
Removed

Red Maj Flashing

Red

Green

Off

Check communication path
from alarm cards to QS941
controller. If no controller is
present, set alarm card rotary
switch to position 0 for contact
closures only communication.

Comm. Fail

Alarm Card
Removed

Red

Maj

Green

Flashing
Red

Replace Alarm card.

None

Standby

Green

Green

Yellow

Remove unit from standby if
desired using QS941 or
Ethernet interface

Circuit Fail

Open Fuse

Yellow

Min Yellow Min Green Flashing

Yellow

Replace unit. Note: Restoring
service to one line will
interrupt service to the other
line served by that card.

Circuit Fail

Under
Voltage

Yellow

Min Yellow Min

Flashing
Yellow

Replace unit. Note: Restoring
service to one line will
interrupt service to the other
line served by that card.

Fan Fail

1 Fan Tray
Failed

Yellow

Min Yellow Min Green Off Replace

fan

tray.

Fan Fail

1 of 6 fans
Failed on
one Fan
Tray

Yellow

Min Yellow Min Green Off Replace

fan

tray.

Fan Fail

2 Fan
Trays
Failed

Red Maj Red Maj Green Off Replace

fan

trays.

Input Power

A1-8
Power Fail

Yellow

Min A

Red Min Green Off

Reconnect DC input power
flowing to the A1-8 input
terminal.

Input Power

B1-8
Power Fail

Yellow

Min B

Red Min Green Off

Reconnect DC input power
flowing to the B1-8 input
terminal

Input Power

A9-16
Power Fail

Yellow

Min A

Red Min Green Off

Reconnect DC input power
flowing to the A9-16 input
terminal

TECHNICAL SUPPORT GUIDE CC84885345