Once both the “A” and the “B” input power LEDs are green, other LEDs can be used to
diagnose other faults.

One fault that may show as a red flashing ALM LED on the alarm card is communications fail.
The flashing red ALM light on the alarm card indicates that it is configured to expect a controller
and is not seeing one.

The Shelf ID rotary DIP switches are as shown here:

[CPS3200U Page 53]

If there is no controller present, the flashing red LED can be addressed by switching the Tens and Units
rotary switches to positions 0 using a small Phillips screwdriver. If a controller is present the signal
between the alarm card and the controller is likely broken. Please examine all wiring. Also note: all
shelves in a system must have different addresses to be recognized by the controller.

8

TECHNICAL SUPPORT GUIDE CC84885345

CPS3200U, QS982A, QS941A, Upstream Systems