[CPS3200U Page 52]

Converter LEDs look like this:

LED Display

Conditions
(on b circuit)

Action Required

All OK

None

Circuit Placed in Standby

None depending on desired
state of circuit b. Standby state
can be set using the QS941
controller or web browser.

Loss of comm.

Check seating on Alarm card
and converter card

Ground fault

Check 5 pin protectors and
faults to ground

Overcurrent or under
voltage

Check output lines for shorts
to each other

OV or internal failure

Replace unit

Thermal Alarm

Solve Thermal problem

card not powered or input
fuse failure

Check source voltage

Lamps test requested from
controller

Observe Lamp Test