secondary disconnect block through to the trip unit wiring
harness connector.

c.

If the breaker’s lower studs connect to the power source,
then the neutral sensor must have its load end connected
to the source.

d.

Verify that the neutral conductor is carrying only the
neutral current associated with the breaker’s load current
(the neutral is not shared with other loads).

5.

If the preceding steps fail to identify the problem, then
measure the sensor resistances. The appropriate values are
listed in Table 1. Since the phase and neutral sensors are
electrically identical, their resistances should agree closely.

Breaker

CT Rating, A

Resistance,

LA-600

150
225
600

10.1–15.2

14.5–22

47–58

LA-1600

800

1600

54–81

110–166

Table 1. CT resistance values.