Figure 9. Primary contact penetration and wipe
PowerVac
®
5kV Vertical Lift
Chapter 4. Installation
Final
Position
1/2” to 5/8”
Electrical
Wipe
Initial
Electrical
Contact
3/4” to 7/8”
Travel
3000A Contact
Wipe area should
be a minimum of
60% contact width
1200A & 2000A
Contact Wipe
should be a line
1/16” to 1/8”
wide.
(grease wipe)
8 3/16 M 26 9 3/4 M 36
12 3/4 M 36HH