Powervac, 3 contact gap adjustment – GE Industrial Solutions PowerVac 5kV VL PV VL 4.16-250-0 User Manual

Page 36

Advertising
background image

36

PowerVac

®

5kV Vertical Lift

Chapter 11. Mechanical Adjustments

Figure 31. Contact Gap measurement, wipe indicator check and wipe measurement

Figure 30. Contact Gap Adjustment—Opening Buffer

1. Buffer Arm
2. Buffer
3. Shims
4. Buffer Stem
5. Bolts

11-3 Contact Gap Adjustment

The gap adjustment refers to the separation, or
gap, between the primary contacts within the
vacuum interrupter. Before attempting to mea-
sure or set the gap adjustment, verify that the
wipe settings are within acceptable limits. Any
change of the wipe settings will affect the gap
settings.

1. With the breaker in the open position and

the closing spring discharged, the buffer
arm should be stopped against the buffer.
Pressing the stem into the buffer.

2. To verify contact gap dimensions, reference

Figure 31.

Advertising