MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

17

Figure 14. Trip Unit display for short-time pickup coupled with

long-time pickup.

The time-current curve for short-time pickup is
shown in Figure 15.

Figure 15. Time-current curve illustrating short-time pickup.

Short-Time Delay

The Trip Unit display for short-time delay is shown
in Figure 16. This function delays the breaker trip on
a short-time trip. The choices of time-delay bands
are listed in Table 12. The delay with

I2T IN

is for a

current of 600% of

xLT at the lower limit of the

band. The delay with

I2T OUT

is for the lower limit of

each band.

On ANSI Trip Units ordered with the user-selectable,
switchable instantaneous overcurrent and ground-
fault option, “X,” an additional value of

OFF

appears

at the end of the delay band settings. Choosing

OFF

disables short-time protection. The short-time

OFF

band is interlocked with instantaneous pickup, so
that only one function can be turned off at a time.

The

I2T OUT

function, illustrated in Figure 17, estab-

lishes a constant time delay.

I2T IN

biases the delay

with a constant slope, as shown in Figure 18.

Figure 16. Trip Unit display for short-time delay.

B

B

B

Baa

a

an

n

n

nd

d

d

d

T

T

T

Tiiiim

m

m

meee

e D

D

D

Deee

ellllaa

a

ayyyyssss,,,, sssseee

eccc

c

1

0.10

2

0.21

3

0.35

Table 12. Lower-limit delays for

I2T OUT

short-time delay bands.

Figure 17. Time-current curve for short-time delay with

I2T OUT

.

Figure 18. Time-current curve for short-time delay with

I2T IN

.