MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 4. Status Mode

31

Ground-Fault Display

When a ground-fault trip occurs, the display illus-
trated in Figure 62 appears. The fault current is dis-
played in units of

xCT, the breaker CT sensor rating.

Multiply the sensor rating of the breaker by the dis-
played fault current multiplier to obtain the ground-
fault current at trip.

Figure 62. Trip Unit status display for ground-fault trip.

Protective-Relay Fault Display

After a protective-relay trip, the display indicates

FAULT

with a target for the type of relay that initiated

the trip. This is illustrated in Figure 63 for an
overvoltage trip. The targets for the five protective
relays are listed in Table 18.

Figure 63. Trip Unit status display for protective-relay trip.

C

C

C

Co

o

o

od

d

d

deee

e

P

P

P

Prrrro

o

o

otttteee

eccc

cttttiiiivvvveee

e R

R

R

Reee

ellllaa

a

ayyyy

V

Voltage unbalance

I

Current unbalance

V

<

Undervoltage

V

>

Overvoltage

I
I

Power reversal

Table 18. Trip Unit display targets for protective relays.

Shunt Trip and Undervoltage Release Trip
Displays (RMS9D Series Trip Units Only)

When a Power Break ®II breaker trips due to the
Shunt Trip, Shunt Trip with Lockout, or
Undervoltage Release, the display indicates the trip
with a flashing target, as illustrated in Figure 64. The
indications

ST

and

UVR

appear for Shunt Trip and

Undervoltage Release trips, respectively. Note that
the

FAULT

segment does not display, since the trip

originated external to the breaker and may not
represent a true fault condition.

Figure 64. Trip Unit status display for Undervoltage Release

trip.

Clearing the Trip Information

Since trip information is stored in nonvolatile mem-
ory, the Trip Unit continues displaying the trip
information until it is manually cleared or a new trip
occurs. After the trip information has been recorded
or reviewed, it can be cleared with the keypad. With
the Trip Unit in Status mode, hold down the

VALUE

key and press the

SELECT

key. The trip information is

then cleared and the display reverts to

STATUS OK

, as

in Figure 56.

Trip Operations Counter Display

Trip operations counters record the total number of
overcurrent trips. To review any of the trip opera-
tions counters while in Status mode, press the

SELECT

key until the desired count appears. Figure 65
illustrates a typical trip operations counter display.
This example indicates that there have been three
long-time trips on this breaker since the counter was
last reset.