GE Industrial Solutions MicroVersaTrip PM User Manual

Page 34

Advertising
background image

MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

24

Figure 45. Accessory configuration switch on rear of Trip Unit,

showing factory settings (solid part indicates that switch is

pushed in on that side).

Description of Switch Settings

Following are descriptions of the effects of each
accessory switch when it is

enabled:

1

1

1

1.... When a Shunt Trip or Shunt Trip with Lockout

accessory causes the breaker to trip, the
contacts of the Bell Alarm–Alarm Only also
change state. The factory switch setting is
disabled.

2

2

2

2.... When an Undervoltage Release accessory

causes the breaker to trip, the contacts of the
Bell Alarm–Alarm Only also change state. The
factory switch setting is

disabled.

SS

S

Sw

w

w

wiiiittttccc

ch

h

h

h

F

F

F

Faa

a

accc

ctttto

o

o

orrrryyyy

SS

S

Seee

ettttttttiiiin

n

n

ng

g

g

g

F

F

F

Fu

u

u

un

n

n

nccc

cttttiiiio

o

o

on

n

n

n

1

Disabled

Shunt Trip or Shunt Trip with

Lockout activates Bell
Alarm–Alarm Only

2

Disabled

UVR trip activates Bell

Alarm–Alarm Only

3

Enabled

Protection trip activates Bell

Alarm–Alarm Only

4

Disabled

Shunt Trip or Shunt Trip with

Lockout activates Bell Alarm with
Lockout

5

Disabled

UVR trip activates Bell Alarm with

Lockout

6

Enabled

Protection trip activates Bell

Alarm with Lockout

Table 17. Accessory configuration switch settings, including

factory defaults.

3

3

3

3.... When a protection trip (long-time, short-time,

instantaneous, ground-fault, or protective-
relay) occurs, the contacts of the Bell
Alarm–Alarm Only also change state. The
factory switch setting is

enabled.

4

4

4

4.... When the Shunt Trip or Shunt Trip with

Lockout accessory causes the breaker to trip,
the contacts of the Bell Alarm with Lockout
also change state. The factory switch setting is
disabled.

5

5

5

5.... When the Undervoltage Release accessory

causes the breaker to trip, the contacts of the
Bell Alarm with Lockout also change state. The
factory switch setting is

disabled.

6

6

6

6.... When a protection trip (long-time, short-time,

instantaneous, ground-fault, or protective-
relay) occurs, the contacts of the Bell Alarm
with Lockout also change state. The factory
switch setting is

enabled.

To change switch settings on RMS9D series Trip
Units, refer to Chapter 5 to remove the Trip Unit
from the breaker. Push in the appropriate Enable or
Disable side of the switch to configure the accesso-
ries, as shown in Figure 46, and carefully reinstall the
Trip Unit. Verify that the new switch settings are
correct by testing the breaker responses to
Undervoltage Release trips and Shunt trips.

Figure 46. Setting the accessory configuration switches.