GE Industrial Solutions MicroVersaTrip PM User Manual

Page 29

Advertising
background image

MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

19

Figure 22. Time-current curve for ground-fault pickup.

Ground-Fault Delay

This function sets the delay before the breaker trips
when the ground-fault pickup current has been
detected. The Trip Unit display is shown in Figure
23. The choices are listed in Table 15. The delay for

I2T OUT

is at the lower limit of each band. The delay

for

I2T IN

is at 200% of the pickup setting at the lower

limit of the band.

The

I2T OUT

function establishes a constant time

delay, as shown in Figure 24.

I2T IN

biases the delay

with a constant slope, as shown in Figure 25.

With the X or GD options (switchable ground fault),
an

OFF

selection appears as an additional time-delay

set point. Selecting

OFF

disables ground-fault protec-

tion.

Figure 23. Trip Unit display for ground-fault delay, showing

I2T

out.

B

B

B

Baa

a

an

n

n

nd

d

d

d

T

T

T

Tiiiim

m

m

meee

e D

D

D

Deee

ellllaa

a

ayyyy,,,, sssseee

eccc

c

OFF

Disabled

1

0.10

2

0.21

3

0.35

Table 15. Lower-limit delays for ground-fault delay bands.

Figure 24. Time-current curve for ground-fault delay with

I2T

OUT

.

Figure 25. Time-current curve for ground-fault delay with

I2T IN

.

Voltage-Unbalance Relay Pickup

This function compares the highest or lowest phase
voltage with the average of all three phases and
initiates a trip if the difference exceeds the set point.
The true rms voltage is computed for each phase.
The range of set points is from 10 to 50% of the
unbalance, with an increment of 1%. The Trip Unit
display is shown in Figure 26.

Advertising