Programmer Disconnect — Accessory Manual for Retrofil CB

DEH-41532 02/12

Figure 10. AKD-6—Holes Drilled for Mounting

Programmer Disconnect

Figure 11. AKD-6—Programmer Disconnect Assembly

Secured in Place

AKD-8—Programmer Secondary Disconnect

• Turn off all power to switchgear. Tagout

and lockout main source, up-stream or
main breaker.

• Failure to comply with these instructions

will result in death or serious injury from
severe burns caused by arc flashing that
has exceedingly high temperatures.

• Always wear personal protection equipment

according to OSHA standards and appropriate
to the severity of potential burns.

• Ensure only qualified personnel install, operate, service, and maintain all electrical equipment.

CAUTION:
WIRING

• Before installing the breaker, the programmer disconnect must be wired to the EntelliGuard Breaker.
• Wires with wire markers are provided on the retrofill. Make sure that the switchgear wiring connection

points match up with the original wiring of the cubicle. This ensures that all wiring connections are
properly made.

• Wrong connections will cause the breaker to malfunction.