Akd-8—programmer secondary disconnect – GE Industrial Solutions Programmer Disconnect User Manual
Page 9
8
Programmer Disconnect — Accessory Manual for Retrofil CB
DEH-41532 02/12
Figure 10. AKD-6—Holes Drilled for Mounting
Programmer Disconnect
Figure 11. AKD-6—Programmer Disconnect Assembly
Secured in Place
AKD-8—Programmer Secondary Disconnect
• Turn off all power to switchgear. Tagout
and lockout main source, up-stream or
main breaker.
• Failure to comply with these instructions
will result in death or serious injury from
severe burns caused by arc flashing that
has exceedingly high temperatures.
• Always wear personal protection equipment
according to OSHA standards and appropriate
to the severity of potential burns.
• Ensure only qualified personnel install, operate, service, and maintain all electrical equipment.
CAUTION:
WIRING
• Before installing the breaker, the programmer disconnect must be wired to the EntelliGuard Breaker.
• Wires with wire markers are provided on the retrofill. Make sure that the switchgear wiring connection
points match up with the original wiring of the cubicle. This ensures that all wiring connections are
properly made.
• Wrong connections will cause the breaker to malfunction.