Drive terminal board i/o – GE Industrial Solutions AF-650 GP MultiPulse Drive Panel User Manual

Page 12

Advertising
background image

MULTIPULSE DRIVE PANEL

12 GE Energy ©2012 GE Company All Rights Reserved

4 Drive

Terminal Board I/O


Any of the AF-600 FP and AF-650 GP terminal
board I/O points which are not already in use
for proper operation of the bypass panel are
available for customer use. The meanings and
connection diagrams for these I/O points are
well described and illustrated in the

DET - 767

AF- 650 GP Design and

Installation Guide

DET - 618

AF- 650 GP Programming

Guide

DET - 768

AF-600 FP Design and

Installation Guide

DET - 620

AF-600 FP Programming Guide


Which are supplied with your panel
documentation package. However there are
several I/O points, which will find frequent use
in panel applications that they are described
below for convenience.

Relay 1 – 01, 02, 03
Programmable contacts

Relay 2 – 04, 05, 06
Programmable contacts.

20, 21, 22, 50, 53, 55

Used for drive speed reference inputs. The
speed pot can be connected to points 50, 53,
and 55. The customer supplied 0-10 VDC or 4-
20 mA signal can also be utilized. Customer
supplied 0-10 VDC signal is connected to
points 20 and 22. Customer supplied 4-20 mA
signal is connected to points 20 and 21.



29 and 12

Used for issuing preset speed command to
drive. The speed at which the motor will run
can be set via drive function code C20.

1, 2, 3, 4, 5
DEVICE NET

62, 63, 66, 67, CS

PROFIBUS/BACNET


79, 80
LONWORKS

68, 69, 61

RS485 Port


39, 42
Analog output

27 Digital output
(Drive Ready)

Advertising