Table 7.2 – GE Industrial Solutions AF-650 GP MultiPulse Drive Panel User Manual

Page 23

Advertising
background image

MULTIPULSE DRIVE PANEL

23 GE Energy ©2012 GE Company All Rights Reserved

Table 7.2

460 VAC Panel Current Ratings and

Maximum Allowable Fuse Sizes

Panel HP

Rating

Panel Current

Rating (Amps)

Maximum

Allowable Fuse

Size (Amps)

1

2.1

3.7

2

3.4

6.0

3

4.8

8.4

5

8.2

13.3

7.5

11

19.3

10

14.5

24.5

15

21

36.8

20

27

47.3

25

34

59.5

30

40

70.0

40

52

91.0

50

65

113.8

60

80

134.8

75

105

168.0

100

130

217.0

125

160

273.0

150

190

320.3

200

240

420.0

250

302

528.5

300

361

631.8

350

443

763.0

450

540

929.3

500

590

1032.5

550

678

1167.3

600

730

1256.5

650

780

1352.8

750

890

1541.8

900

1050

1828.8

1000

1160

2009.0

1200

1380

2409.8

1350

1530

2649.5