GE Industrial Solutions AF-650 GP MultiPulse Drive Panel User Manual

Page 21

Advertising
background image

MULTIPULSE DRIVE PANEL

21 GE Energy ©2012 GE Company All Rights Reserved

TEST CHART for VFD with diodes connected to BUS CAPACITORS

Diode Meter RED

Diode Meter BLK

Expected

Actual

L1

+DC Bus

0.2-0.6VDC

L2

+DC Bus

0.2-0.6VDC

L3

+DC Bus

0.2-0.6VDC

+DC Bus

L1

Charging

+DC Bus

L2

Charging

+DC Bus

L3

Charging

L1

-DC Bus

Charging

L2

-DC Bus

Charging

L3

-DC Bus

Charging

-DC Bus

L1

0.2-0.6VDC

-DC Bus

L2

0.2-0.6VDC

-DC Bus

L3

0.2-0.6VDC


TEST CHART for (R2, S2, T2) or (2,5,8) with Bus removed

Diode Meter RED

Diode Meter BLK

Expected

Actual

R2

+DC Bus Cathode

0.2-0.6VDC

S2

+DC Bus Cathode

0.2-0.6VDC

T2

+DC Bus Cathode

0.2-0.6VDC

+DC Bus Cathode

R2

Open

+DC Bus Cathode

S2

Open

+DC Bus Cathode

T2

Open

R2

-DC Bus Anode

Open

S2

-DC Bus Anode

Open

T2

-DC Bus Anode

Open

-DC Bus Anode

R2

0.2-0.6VDC

-DC Bus Anode

S2

0.2-0.6VDC

-DC Bus Anode

T2

0.2-0.6VDC


TEST CHART (R3, S3, T3) or (3,6,9) with Bus removed

Diode Meter RED

Diode Meter BLK

Expected

Actual

R3

+DC Bus Cathode

0.2-0.6VDC

S3

+DC Bus Cathode

0.2-0.6VDC

T3

+DC Bus Cathode

0.2-0.6VDC

+DC Bus Cathode

R3

Open

+DC Bus Cathode

S3

Open

+DC Bus Cathode

T3

Open

R3

-DC Bus Anode

Open

S3

-DC Bus Anode

Open

T3

-DC Bus Anode

Open

-DC Bus Anode

R3

0.2-0.6VDC

-DC Bus Anode

S3

0.2-0.6VDC

-DC Bus Anode

T3

0.2-0.6VDC

Advertising