PRODUCT DESCRIPTION:

GE TRANQUELL Series Type 2 Surge Protective Devices (formerly called TVSS), are for installation

on low voltage electrical distribution systems. GE SPDs are designed to protect electrical

equipment loads against the damaging effects of transient voltages that can be induced or

generated as a result of remote lightning, power equipment switching or high frequency

disturbances.

The TRANQUELL Series SPD incorporate Metal Oxide Varistor (MOV) technology to achieve

superior transient suppression performance. Integral to the SPD is a patented thermal fusing

system that offers SPD circuit interruption in the event of a limited current abnormal overvoltage

condition. Other standard features include protection status indicating lights and form C alarm

contacts for remote monitoring. TME models also include surge rated fuses and built in EMI

filtering.

The GE Tranquell SPD units described in this manual are enclosed, wall mounted styles that are

UL/cUL Listed, conforming to UL 1283 and UL 1449 3

rd

Edition where applicable. All published

ratings are in accordance with ANSI / IEEE C62.41.1-2002, C62.41.2-2002 and NEMA LS1-1992

(R2000) recommended guidelines.

Model covered by this manual are:

GE Tranquell TLE and TME model types ending with the part number suffix WM, WMF, or WM4

(Examples: TLE120Y050WM, TME277Y100WMF, TLE240D025WM4)

APPLICATION GUIDELINES:

Determining the surge protection to be provided in a facility or for a particular system or

equipment can be a complex task that should be addressed as early as possible. This is typically

when a new facility is constructed or sensitive electronic equipment has been installed. The

following guidelines are offered for application assistance:



Prior to installing any SPD, ensure that your facility electric supply system is properly

installed and connected in accordance with all applicable national and local codes and

safety procedures. All equipment and systems should be installed in accordance with

manufacturer’s instructions.



Utilize the personnel from your local utility, your engineering department, GE application or

service engineering, or a professional consulting engineering firm for technical guidance or

troubleshooting.



Understand your system, and the capabilities and limitations of SPD and other power

conditioning equipment.



Select the proper GE Tranquell Series SPD unit for your system voltage, configuration, and

the anticipated surge environment. Some of the key parameters for selection are defined

below:

 SPD T

YPE

The SPDs covered in this document are rated and marked accordingly for use on Type 2

applications. Type 2 SPDs can be installed only on the load side of the electrical distribution

system’s main breaker or fuse.