Voltage ratings & power source configurations – GE Industrial Solutions Tranquell Series Low and Medium User Manual

Page 7

Advertising
background image

2020005003 (12/09) Page 7 of 18

















































Three Phase

Delta Hi-Leg,

4 Wire + Ground

150V (L-N / L-G)

Phase A & C

270V (L-N / L-G)

Phase B

120 / 240V

TLE / TME 240H

Three Phase

Delta,

3 Wire

Three Phase

WYE,

3 Wire

270V (L-G)

550V (L-G)

240V

480V

TLE / TME 240D

TLE / TME 480D

Three Phase

WYE,

4 Wire + Ground

150V (L-N / L-G)

320V (L-N / L-G)

320V (L-N / L-G)

320V (L-N / L-G)

120 / 208V

220 / 380V

240 / 415V

277 / 480V

TLE / TME 120Y

TLE / TME 220Y

TLE / TME 240Y

TLE / TME 277Y

Single Phase

3 Wire + Ground

Dual Phase

3 Wire + Ground

150V (L-N / L-G)

120 / 208-

240V

TLE / TME 120S

SOURCE

CONFIGURATION

SYSTEM

TYPE

MAXIMUM

CONTINOUS

OPERATING VOLTAGE

(MCOV)

NOMINAL

VOLTAGE

(50/60Hz)

TRANQUELL

MODEL

VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS

L1

L2

N

L1

L2

N

L1

L2

L3

N

L1

L2

L3

L1

L2

L3

L3

L1

L2

N