Warning – GE Industrial Solutions Tranquell Series Low and Medium User Manual

Page 6

Advertising
background image

2020005003 (12/09) Page 6 of 18

PRE-INSTALLATION REQUIREMENTS:

Prior to energization of the GE Tranquell SPD, it is critical that the following items have been

addressed.

DO NOT ATTEMPT TO ENERGIZE THE SPD OR CONTINUE WITH THE INSTALLATION IF

ALL OF THESE CONDITIONS HAVE NOT BEEN MET, OR ARE UNKNOWN.

1.

SYSTEM CONFIGURATION AND VOLTAGE

Check the configuration and voltage supply ratings to ensure that the proper SPD model

number has been selected for your system. The SPD model number can be found on the UL

label affixed to the SPD NEMA Enclosure. The SPD selection can be verified by comparing the

Model Number to the correct electrical system described in theVOLTAGE RATINGS & POWER

SOURCE CONFIGURATIONS” chart shown on page 7.

2.

SYSTEM GROUNDING AND BONDING

Verify that a NEC (National Electrical Code) compliant X0 bond has been made at the

upstream transformer or other separately derived system that feeds the SPD. Per NEC

Article 250.30, this bond must be in place on all 3-Phase WYE, 3-Phase Hi-Leg Delta, and

Single Phase Split-Systems. Refer to page 8 for an example of an installation that complies

with these NEC recommendations.

Verify that there have not been multiple instances of Neutral to Ground bonds on the

electrical system. These bonds, while either intentional or accidental, result in Ground

currents that can create differential voltage potentials between Neutral and Ground.

Redundant Neutral to Ground connections can result in damage to the SPD and are in

violation of NEC.

3.

SPD INSTALLATION ON UNGROUNDED POWER SYSTEMS

Ungrounded power systems are inherently unstable and can produce excessively high line-

to-ground voltages during certain fault conditions. During these fault conditions any

electrical equipment, including an SPD, may be subjected to voltages which exceed their

designed ratings. This information is being provided to the user so that an informed decision

can be made before installing any electrical equipment on an ungrounded power system.

4.

SPD LOCATION / PRIMARY OVERCURRENT PROTECTION

Per the National Electrical Code (NEC Article 285), Type 2 SPDs may be placed only on the

load side of the main service breaker or fuse at each utility service entrance or separately

derived power system.

WARNING

THE EQUIPMENT COVERED BY THESE INSTRUCTIONS SHOULD

BE

INSTALLED

AND

SERVICED

ONLY

BY

COMPETENT,

QUALIFIED PERSONNEL UTILIZING PROPER SAFETY PRACTICES

AND PROCEDURES THESE INSTRUCTIONS ARE WRITTEN FOR

SUCH PERSONNEL AND ARE NOT INTENDED AS A SUBSTITUTE

FOR

ADEQUATE

TRAINING

AND

EXPERIENCE

IN

SAFE

PROCEDURES FOR THIS TYPE OF EQUIPMENT.

WARNING

FAILURE TO PROVIDE THE X0 BOND WILL DAMAGE THE

SPD AND VOID THE PRODUCT WARRANTY.

Advertising