GE Industrial Solutions ASPMETER Install User Manual

Aspmeter, Notice, Danger

Advertising
background image

Z206024-0B

PAGE 1

©2011 For technical support please contact

10111

DET-756

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

TM

POWER MONITORING

INSTALLATION GUIDE

ASPMETER

Installer’s Specifications

Performance:

System Accuracy (Branch Circuits Included)

Current

1% of reading from 2.0-100 A, 2% of reading from 0.25-2A

Power

3% of reading from 1-100%*

Mains Accuracy

Voltage

1% of reading from 90-277 VAC L-N

Power (Aux Input)

IEC 61036 Class 1

Current (Aux Input)

2% of reading from 1-10% of CT rating;

1% of reading from 10-100% of CT rating (0.333 VAC)

Operation:

Input Voltage

90-277 VAC

Frequency

50/60 Hz

Sampling Frequency

2560 Hz

Update Rate

1.8 seconds (both panels)

Overload Capability

22 kAIC

Ribbon Cable Support

up to 20 ft. (6 m) available (flat or round)

(sold

separately)

Operating Temperature Range

0° to 60°C (32° to 140°F) (<95% RH, non-condensing)

Storage Temperature Range

-40° to 70°C (-40° to 158°F)

Network Communications:

Type

Modbus RTU

Connection

DIP switch-selectable 2-wire or 4-wire, RS-485

Address

DIP switch-selectable address 1 to 247 (in pairs of 2)**

Baud Rate

DIP switch-selectable 9600, 19200, 38400

Parity

DIP switch-selectable NONE, ODD, EVEN

Communication Format

8-data-bits, 1-start-bit, 1-stop-bit

Termination

5-position depluggable connector

(TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Note: Standard IEC62053-21 Table 8 temperature coefficients apply for temperatures above and

below 25°C.

* Add 1% for 0.8 PF to 0.5 PF.

** See Configuration section for details.

Panelboard Monitoring System

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

• Follow safe electrical work practices.

See NFPA 70E in the USA, or applicable local codes.

• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• The installer is responsible for conformance to all applicable codes.

• Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE: This equipment has been tested by the manufacturer and found

to comply with the limits for a class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in
a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of
Veris Industries nullify this statement.

PRODUCT IDENTIFICATION

QUICK INSTALL

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

1. Disconnect and lock out power. Use a properly rated voltage sensing device to

confirm power is off.

2. Mount current sensor strips adjacent to breaker terminations.

3. Verify that the serial numbers on the CTs match that on the board.

4. Configure communication and addressing parameters using DIP switches.

5. Mount the main acquisition board in the electrical enclosure.

6. Connect current sensor strip cables to the main board, observing the 2-strip setup

and their orientation (A or B) within the panel.

7. Wire RS-485 communications.

8. Connect CTs to the auxiliary inputs and connect them onto the main conductors in

the enclosure (optional).

9. Wire control power and voltage taps (ASPMETERA and ASPMETERB only).

10. Download the free E3x Configuration Tool from www.veris.com to commission the

device for operation.

ASPMETER

LISTED

44XJ

IND:CONT EQ

ASPMETER

*Each strip contains
21 current sensors.

Description

A = Advanced
B = Intermediate
C = Basic

# of CTs

42 = 2 strips*

42

AQ = THQB circuit breakers
AE = TEY circuit breakers