APPENDIX A:
MECHANICAL INSTALLATION

Observe handling precautions for static sensitive

devices to avoid damage to the circuitry which

would not be covered under the factory warranty.

Disconnect power to the electrical panel and lock it out.

1. Install the current sensor strips in the panel (Figure 1).

2. Arrange the sensor strips in one of the four configurations shown in Figure 2.

Adjust orientation of the circuit numbers in the field during commissioning by
writing to Modbus Register 6 or use free configuration software at www.veris.
com.

Figure 1

CTs accept a maximum #2 AWG (0.384” O.D.)

wire with THHN insulation.

Use this gauge wire or smaller for 100 A circuits.

E30 CURRENT SENSOR STRIP

E30 CURRENT SENSOR STRIP

20

20

20

20

20

20

20

20

20

2020

20

20

20

20

20

20

20

20

20

20

20

1
5
9
13
17
21
25
29
33
37
41

3
7
11
15
19
23
27
31
35
39

2
6
10
14
18
22
26
30
34
38
42

4
8
12
16
20
24
28
32
36
40

A

B

1
5
9
13
17
21
25
29
33
37
41

3
7
11
15
19
23
27
31
35
39

2
6
10
14
18
22
26
30
34
38
42

4
8
12
16
20
24
28
32
36
40

A

B

1
3
5
7
9
11
13
15
17
19
21

2
4
6
8
10
12
14
16
18
20

22
24
26
28
30
32
34
36
38
40
42

23
25
27
29
31
33
35
37
39
41

2
6
10
14
18
22
26
30
34
38
42

4
8
12
16
20
24
28
32
36
40

1
5
9
13
17
21
25
29
33
37
41

3
7
11
15
19
23
27
31
35
39

A

B

A

B

A
B

A
B

A
B

A
B

A
B

Top Feed

Bottom Feed

Single Row: Sequential

Single Row: Odd/Even

Register 6
Value = 0

(Default)

Register 6
Value = 1

Register 6
Value = 2

Register 6
Value = 3

Figure 2