Installation guide, Wiring, Aspmeter – GE Industrial Solutions ASPMETER Install User Manual

Page 4: Wire 4-wire 2-wire example, Shield rx- tx- rx+ tx+ tx- tx

Advertising
background image

TM

ASPMETER

INSTALLATION GUIDE

Z206024-0B

PAGE 4

©2011 For technical support please contact

10111

DET-756

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

WIRING

Power must be disconnected and locked out before making any wiring connections.

Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 9 and 10).

Figure 9

Figure 10

SHIELD
RX- TX-
RX+ TX+
TX-
TX+

Master or Slave

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

SHIELD

Master

Slave

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

2-Wire

4-Wire

2-Wire Example

Figure 11

+

Belden 1120A or

equivalent

120 Ω terminator

on last device of

daisy chain

Not Used

WARNING: After wiring the RS-485 cable, remove all

scraps of wire or foil shield from the electrical panel.

Wire scraps coming into contact with high voltage

conductors could be DANGEROUS!

+

1. Mechanically secure the RS-485 cable where it enters the electrical panel.

2. Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the

chain (Figure 11).

3. Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. The cable

must be voltage-rated for the installation.

4. When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6

N·m (0.37 to 0.44 ft·lb ) for connectors on main board, 0.22 to 0.26 N·m (0.16 to
0.19 ft·lb) for connectors on adapter boards (Figure 12).

Figure 12