CONFIGURATION

1. Communications Configuration: Communications parameters for the ASPMETER

series are field selectable for your convenience. Please see the Product Diagram
section (page 2) for selector location. The following parameters are configurable:

• Baud Rate: 9600, 19200, 38400
• Parity On or Off
• Parity: odd or even
• Wiring: two or four

B

ø

Reserved

B1 Off/

On

Parity

2/4

Wire

Odd/
Even

Parity

Example: 2-wire 19200 Baud No Parity (Default Only)

1

2

3

4

5

6

7

8

off

off

X

X

X

9600

on

off

X

X

X

19200

off

on

X

X

X

38400

on

on

X

X

X

Reserved

off

off

X

X

X

No Parity

on

off

X

X

X

Odd Parity

off

on

X

X

X

No Parity

on

on

X

X

X

Even Parity

on

X

X

X

4-wire RS-
485

off

X

X

X

2-wire RS-
485

2. Address Configuration: Each Modbus device on a single network must have a

unique address. Set the switch block to assign a unique address before the device
is connected to the Modbus RS-485 network. If an address is selected which
conflicts with another device, neither device will be able to communicate.

3. Address the ASPMETER as any whole number between and including 1-246. Each

unit is equipped with a set of 8 DIP switches for addressing. See below.

1

LSB

MSB

1 2 4 8 16 32 64 128

DIP Switch Values

=

4. To determine an address, simply add the values of any switch that is on.

For example:

40

=

LSB

MSB

Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.

(8 + 32 = 40). Therefore, the address for the ASPMETER is 40.

See the Address Setup section (page 8) for a pictorial listing of the first 63 switch
positions.

DEFAULT DIP SWITCH SETTINGS

The ASPMETER includes two DIP switches, as shown below. Switches are shown in
their default positions.

Comms Address

Comms Settings