Adjustments – GE Industrial Solutions AF-600 FP Redundant Drive Panels User Manual

Page 14

Advertising
background image


DEH40634

AN 11-1018 Rev.02, 09/26/2011


Relay 1 – 01,02,03

Normally open inverter fault contacts. These contacts are utilized to energize
an interposing relay for bypass panel control logic and to provide customers

with a drive fault status via higher rated normally open contacts than those

inherent to the drive.


Relay 2 – 04,05,06

Normally open programmable contacts. These contacts have been
configured to provide a drive running status for customer use. This status is

then used to energize an interposing relay to provide customers with drive

running status via higher rated normally open contacts than those inherent to

the drive. .


54, 55

Used for drive speed reference inputs


29

Jog (Digital input)
Drive will be programmed (Parameter C20) to run at preset speed (50Hz jog

frequency)


1,2,3,4,5

DEVICE NET Communications (with option card)


62,63,66,67,CS

PROFIBUS/BACNET Communications (with option card)


79,80

LONWORKS Communications (with option card)


68,69,61

RS485 Port / Modbus / Metasys / Apogee Communications


4. Adjustments

The AF 600 FP & Redundant Drive panel has several user settable adjustments, which allow it to be tailored

specifically for your 3-phase induction motor. Setting these adjustments appropriately is an important factor

in ensuring that applicable safety codes are met and that your bypass panel, wiring, and motor are

adequately protected. The following list comprises all of the user adjustable devices/components inside the

AF 600 FP & Bypass panel. The user may wish to have a copy of NFPA 70-2008 (commonly known as the

National Electric Code or simply NEC) available for reference when setting these adjustments.



Input Fuses

Main input fuses are provided standard with your AF 600 FP & Redundant
Drive panel. In general there are two configurations that utilize input fuses; 1)

input disconnect with load side separately mounted fuses and 2) input Fused

Disconnect where the fuses are an integral part of the disconnect. If your

panel was ordered with 8% line reactor then it will have main input fuse

connected prior to reactor, This fuses will provide shirt circuit protection for

15HP with 8% reactor or without 8% reactor fusible Disconnector itself will

have integral fuses. The main input fuses provided with your bypass panel

has been closely coordinated to provide short circuit protection for the

inverter along with short circuit and over current protection for the motor. In

“Drive1” or “Drive2” mode of operation, the fuses only provide short circuit

protection due to the fact that the inverter has inherent over current

14