GE Industrial Solutions AF-600 FP Redundant Drive Panels User Manual

Page 5

Advertising
background image

DEH40632

AN 12-1007, Rev.03, 04/04/2012




GROUNDING


All panels/enclosures must be grounded. All exposed metal parts are
connected to ground to prevent contact with a dangerous voltage if
electrical insulations fail.

Each panel contains a grounding bus with provisions for connecting a

field-grounding conductor.

All field wiring shall be copper and have a minimum insulation rating of
75

C (167

F).

Size grounding conductors according to local and national codes

Grounding methods must comply to local and national codes.


POWER WIRE

(Greater than 120 VAC)


All field wiring shall be copper and have a minimum insulation rating of
75

C (167

F).

Size all wire based on panel nameplate current ratings in accordance

with local and national codes. Do not use the cable sizes listed in DET -

609 & DET – 610 manuals.

All power wiring must be routed away from other wiring. Avoid running

power wiring parallel to other wiring without a minimum separation

distance of four (4) inches. Power wiring should only cross perpendicular

to other wiring.

Input and output power shall be connected as per the wiring diagram.

Incoming power cables should be terminated at line side of the lugs

provided with the Disconnect switch.

Locate terminals (T1, T2, and T3) in the panels and use these terminals to

connect the motor wires. Depending on actual drive panel configuration,

motor cables should be terminated on the load side of the Power

Distribution Blocks.

Refer to Appendix B for Tightening torque details for motor connections.

CAUTION: Failure to cover components from metal shavings may

result in damage to equipment.

5

Advertising