CONTROL WIRING

(120 VAC )


All field wiring shall have a minimum insulation rating of 75

C (167

F).

Size wire according to local and national codes.

All control wiring must be routed away from power wiring. If control

wiring is routed parallel to signal wiring (24 Vdc or less), isolation of the

signal wiring must be maintained. A minimum of four (4) inches is needed

to adequately separate signal and control wiring. If signal wire is UL

recognized shielded cable, separation can be minimized to a one (1) inch

separation.

AF-600 Redundant Drive Panels require no additional control wiring to

operate properly. Additional control interfacing to your control panel can

be accomplished through the panel mounted customer terminal board

“CTB1”. Please reference the appropriate wiring diagram. Torque values

for connecting to “CTB1” are located in the Appendices.

SIGNAL WIRING

(24 VDC or less)


All field wiring shall have a minimum insulation rating of 75

C (167

F).

Size wire according to local and national codes.

All field signal wiring must be twisted and shielded. All shields must be

grounded at one point ONLY. It is recommended to terminate the shield

drains at the signal’s source. Avoid routing signal wiring with power

wiring. If signal wiring is routed with control wiring a minimum separation

of one (1) inch is required.

CAUTION: Do not connect power supply voltage greater than panel

rated voltage, or damage will occur to equipment.

WARNING: Never connect or disconnect input wiring with voltage

applied, a serious or fatal injury may result.

WARNING: Never connect or disconnect output wiring with

voltage applied, a serious or fatal injury may result.