DEH40634

AN 11-1018 Rev.02, 09/26/2011


Relay 1

(E24)

Set to “9” Alarm



Relay 2

(E24)

Set to “5”Running


Electronic Overload

(F10)

Set to “4” Elec OL Trip 1


Motor Thermistor Input

(F12)

Set to “0” None


Auto-Reset (Times)

(H04)

Set to “13” Infinite Auto Reset


Drive Programming

Auto-Tune
In the event that it is desired to “auto-tune” the drive to the connected motor, reference the following

instructions along with the AF 600 FP User’s Guide (DET – 609):

With power applied to the panel –

1) Place the Hand/Off/Auto, and Drive1/Off/Drive2 selector switches in the “Off”, and “Drive1” positions

respectively.

2) For Full Auto tuning follow the instruction below

Quick Menu

Ok

Quick start

Ok

Once Up arrow

Ok

P-04 Auto Tuning

Ok

[1] Full Auto tune

Ok

Follow the Keypad direction

Note: If the panel has a load reactor, select “Reduced

Auto tune”.

16