Handle installation – GE Industrial Solutions Cable Operator Mechanisms for Thermal-Magnetic E150 and Spectra SE150, SF250, and SG600 MCCBs User Manual

Page 3

Advertising
background image

Figure 3. Handle Installation.

Handle Installation

1. Referring to Figure 1, Figure 2, and Figure 3,

determine the location of the handle on the flange

of the enclosure. The handle can be mounted on

either the right or left side of the enclosure.

2. If the flange is not provided with handle holes and

slots, drill these as shown in Figures 1 and 2. Remove

any burrs.

3. Position the O-ring [5] in the groove in the handle.

Assemble the handle [1] and the cable adapter

assembly [2] to the flange of the enclosure with two

1

/

4

-20 x

5

/

8

" hex-head screws [3] and lock washers

[4]. Tighten the screws to 35–45 in-lb.

4. Assemble the interlock blade [6] to the handle with

two #8-32 sems screws [7], as shown in Figure 1.

5. Assemble the drive arm extension to the handle drive

link with the connecting pin [12]. Secure the

connection with an E-ring [13], as shown in Figure 3.

6. Attach one end of the handle-return spring [14] to

the hole in the drive link and the drive arm

extension. Attach the other end to the hole in the

lower flange of the cable adapter assembly, as

illustrated in Figure 3.

7. Drill and tap two #8-32 holes in the cover, as shown

in Figures 1 and 3. Assemble the interlock bracket [9]

to the cover with two #8-32 sems screws [7] from

inside the door. Alternatively, the bracket may be

welded to the cover, using the dimensions noted with

an asterisk (*) in Figure 3, to locate the upper-left

corner of the bracket, as illustrated in Figure 1.

8. Assemble the interlock hook [8] to the interlock

bracket [9] with two #8-32 sems screws [7]. Use the

lower set of holes in the hook for a door with a

3

/

4

-

inch turned edge (as shown) or the upper set of

holes if the door has a 1.

1

/

8

-inch turned edge.

9. With the handle in the OFF position, attempt to close

the door. If the interlock blade interferes with the

interlock hook,

DO NOT

force the door closed.

Loosen the two #8-32 screws [7] and move the

interlock hook upward. The door should close

without interference. Attempt to turn the handle ON;

if the handle turns ON, loosen the two #8-32 screws

[7], secure the interlock hook, and move the hook

toward the bottom of the enclosure to provide more

depression of the interlock blade, thus preventing

the handle from engaging.

10. As the handle is moved to the ON position, the

interlock hook should engage the interlock blade,

preventing the door from opening unless the handle

interlock is manually disengaged by rotating

(clockwise) the interlock defeat button with a flat-

blade screw driver on the handle [1]. If the door can

be opened with the handle in the ON position

without having to defeat the interlock blade, readjust

the interlock hook downward and repeat steps 9 and

10.

11. Turn the handle to the OFF position. You should be

able to open the door. Note that if vault-type

interlock hardware (GE Cat. No. TDV1) or a similar

assembly has been installed, the door hardware must

first be defeated.

12. Proceed with installation of the drive cable and the

breaker operating mechanism per the instructions.

Advertising