4.11.1

Switch Alignment and Adjustment Procedure

Step 1: Disconnect Pushrods

Remove cotter pins and clevis pins that connect
pushrods to operating arms of each pole of switch.
See Figure 5.

Step 2: Main Blade Alignment

Disengage switch blades by pulling outward on
the main switch blade until the main blades are
separated from the jaw casting. Continue to pull
outward until arcing blade disengages from the
arc chute. See Figure 6.

If the main blades do not align with the jaw
contacts, loosen the hinge casting mounting bolts
and move the pole assembly. Then re-tighten the
bolts. See Figure 7.

Figure 5

Figure 6

Figure 7

DANGER

Make sure that all power sources are deenergized before attempting any maintenance.

!

WARNING

The arcing blade is under spring

pressure and snaps open when clear of

the stationary arcing contacts within

the arc chute.

!

Hinge casting

BreakMaster Load Interrupter Switch