BreakMaster Load Interrupter Switch

Section 10 – Troubleshooting

Trouble

Cause

Remedy

If the switch is overheated because of excess current,
one of two remedies can be adopted:

Overload

Replace with a switch of rating adequate for
the present or future loads, or:
Rearrange circuits to remove excess load.

Poor Contact
(Contact out of adjustment)

Adjust Contacts (See Section 4.11.1)

Connections to Switch not of

Increase the capacity of the connections by adding

Overheating

adequate current carrying capacity.

conductors or by replacing with heavier conductors.

Contacts Burned or Pitted

Contacts should be dressed and fitted properly.
(See Section 4.11.1)

Bolts and Nuts of

Tighten all bolts and nuts. (Do not exceed torque as

Connections not tight

per Section 4.2 by more or less than 10 percent. Over-
tightening bolts may cause bolts to exceed their elastic
limit, leading to more loosening of the connections.)

Located in too hot an ambient

Relocate in a cooler place or arrange some means

(40°C Max.). (Such as too close to

of cooling.

a boiler, a furnace or the like)

WARNING

Do not exceed 40°C as maximum ambient temperature.

!