BreakMaster Load Interrupter Switch

Sequence of Operation for Controller MX250-LIS
See GE Zenith document 71R-2000A for more details

When Normal Source voltage or frequency

falls below the preset “Fail” values

(P) Time Delay to start Emergency Source

Time Delay (DT) for closing Normal Switch

S2>S1, SOL Timer start

Time Delay (T) to confirm availability of stable

Normal Source (S1). S2>S1, SOL Timer start

Emergency Source Not Available

Nothing Happens. STOP!

Emergency Source Available

S1>S2, SOL timer starts

Normal Source (S1) Switch Open

No

No

Yes

Emergency Switch

stays as is. END!

Yes

Emergency Switch Close

Is Normal Source (S1) available?

Emergency Switch Open

Normal Switch Close

When Normal Source returns

(W) Time Delay to open Normal Source to ensure voltage and frequency stabilization

of Emergency Source before transfers

Time Delay (DW) before closing Emergency Switch.

Is Emergency Source (S2) available?

Emergency Source Stop Delay Time (U) – Cool Down

Transfer to Normal

Source (S1)