3 power supply – GE Industrial Solutions 6KCV301DNET User Manual

Page 9

Advertising
background image

6KCV301DNET

9

——————

Interface card DeviceNet

——————

4.

The Baud Rate of the SBI card is set via the Switches 7 and 8 of the
Dipswitch S1. The Baud Rate is detected only when the card is switched
on and it can be modified only by switching off and swtching on the card
again.Table 2 shows the relation between the DIP-Switches and the se-
lectable Baud Rate value. The Default value is 125 Kbaud.

Switch 8 Switch 7 Baud Rate

OFF

OFF

125 kBaud

OFF

ON

250 kBaud

ON

OFF

500 kBaud

ON

ON

125 KBaud

DN21

.

5.

The switches 1..6 of the Dip-Switch S1 determine the address.

The address is only detected when the card is switched on. If the address
has been modified, the SBI card has first to be switched off and then on in
order assume the new address.

6.

The Dip-Switch S2 determines the amount of words exchanged over the
Polling I/O. The table describes the relationship between the switches and
the number of Polling I/O words.

switch 4

switch 3

switch 2

switch 1

# of Polling I/O word

OFF

OFF

OFF

OFF

1

OFF

OFF

OFF

ON

1

OFF

OFF

ON

OFF

2

OFF

OFF

ON

ON

3

OFF

ON

OFF

OFF

4

OFF

ON

OFF

ON

5

OFF

ON

ON

OFF

6

All

Other

6

tdn0010

Combination

The Polling I/O word number is only detected when the card is switched on. If
the polling I/O word number has been modified, the SBI card has first to be
switched off and then on.

7.

Connect the Bus cable to the BUS terminal.

8.

Switch on the drive.

9.

The LEDS PWR and RUN light up.

10. Switch the Device Net power supply on; the LED H1 lights up.

11. The LED OP lights up when the Master/Slave connection has been established.