GE Industrial Solutions Mini-BDFB User Manual
GE Industrial Solutions Equipment
Installation Guide
Service and Assistance - call +1 877 546 3243 or +1 972 244 9288
© 2012 General Electric Company. All rights reserved.
850027449
Issue 1 December 2012
1
Micro-BDCBB DC Battery Distribution Circuit Breaker Bay
ED83368-30
600 A, −48V / +24V, 19” or 23”
Micro-BDCBB Configurations
Mounting
Fuse/Breaker
Positions
Shunts
Buses
Meter
Ordering Code
Group
Battery
Return
19”
14
-
1
or 2
-
108992070
3
19”
14
2
2
1
VIM1
CC109145455
4
19”
14
2
1
1
VIM1
CC109145447
8
23”
22
-
or 2
1
-
108991056
1
23”
22
2
2
VIM1
CC109145463
2
23”
22
2
1
VIM1
CC109145430
6
Notes:
1. Group 1 – Field conversion to +24V and Dual buses is not supported.
2. Group 3 – Field conversion to +24V is not supported.
1 Shunts, when provided, are two 600A shunts, one on each side - A Bus (left) and B bus (right).
The VIM1 meter sums the two shunts for one battery bus configurations.
2 Factory Configuration – Convert to 2-bus by removing the installed bridging bus bar.