Programming the meter – GE Industrial Solutions Mini-BDFB User Manual

Page 10

Advertising
background image

Micro-BDCBB ED83368-30

850027449 Issue 1 DRAFT December 2012

10

Programming the Meter

VIM1 parameters like shunt size and number of load buses are preconfigured when it is factory installed in a
BDFB/BDCBB or Micro-BDFB. Only customer specific preferences need to be adjusted in the field. As a
replacement or mete upgrade, the factory default settings may need to be adjusted for the application. Listed
below are the configurable parameters and their associated factory defaults available through the front panel.
Following the table are the typical items that need to be configured or verified in a retrofit or replacement
application.

System Parameters

Description

System Voltage

Used to identify system voltage. Selectable between 24V and 48V. Factory default is

48V.

Local Buzzer

Allows the integrated audible alarm to be Enabled or Disabled. Factory default is

Disabled.

Display Contrast

Allows the display contrast to be adjusted for the local ambient lighting. Adjustable

from 0-100% in 1% increments. Factory default is 50%.

Software Version

Displays the version of the application code running in the meter in the format

(vX.Y). Version 1.5 is the latest as of this printing.

Load Parameters

Description

Number Of Loads

Used to identify the number of individual loads/buses in the distribution. Value

configurable from 1-8. Factory default is 6.

Meter Type

Configures meter to display individual monitored bus voltages (voltage), voltages

and currents (volt_curr), or only currents (current). This configuration is defined by

the internal wiring of the distribution. Factory default is Voltage and Current

(volt_curr).

Load ID Format

Configures display format used in referencing individual DC loads/buses.

Allowable formats: A1, A, and 1. “A1” identifies loads using an A1, B1; A2, B2; …

format. “A” identifies loads using an A, B, C, D ... format. “1” identifies loads using a

1, 2, 3, 4 … format. Factor Default is to use the A1 format.

First Load (location)

Used to indicate where the first load in the distribution is located. Allowable

configurations are: top-left, top-right, btm-left (bottom-left), btm-right (bottom-

right). Every monitored shunt is considered a load. Factory default is “top-left”.

Shunt Rating

Used to define the current rating of the shunt in the load bus. All shunts in the

load must be of the same size. A 50mV shunt is assumed. Allowable range is 1-

4000A. The factory default is 800A.

Overload Latch

A single configuration for all panels/buses that allows a temporary Over Load

event to be latched. Factory default is “Disabled”.

Combined Load

Displays the load value as one combined sum by adding up all shunts in the

system and presenting it as values for a single load. Factory default is disabled.

Load Available

(A1-A4;B1- B4)

Indicates if the load is available or in use. Allowable configurations are “installed”

and “not installed”. “Installed” loads imply that the load is in use. “Not Installed”

loads imply that the load may be present, but it is not in use. Information

obtained from the load should not be relevant. Factor default is set to be

“installed”.

Load Power Loss

The Power Loss (PL) alarm is triggered upon loss of the primary DC or when the

individual’s panels’ DC input has reached the configured low voltage threshold.

This Power Loss voltage threshold is configurable between 40.00-60.00V for 48V

systems and 20.00-30.00V for 24V systems. Factory defaults for these thresholds

are 40.00V and 20.00V, respectively.

Load Overload

Type

The Power Overload Type defines whether the smart meter is to treat the

Overload alarm event for a “Single Bus” or for an “Redundant Bus” configuration.

The “Single Bus” configuration is based on straight Overload threshold being

exceeded. The “Redundant Bus” configuration causes the VIM1 to sum the two

respective left and right load shunt measurements and compare it to the

individual overload thresholds configured for the each of the respective panels in

the pairing. The lowest Overload value threshold configured for the Redundant

loads shall take priority and be used in the comparison. Once the “Redundant

Bus” measurement exceeds this threshold, the controller asserts the Over Load

(OVL) alarm. Factor default is “Single Bus” configuration”.

Load Overload

The Load Overload (OVL) alarm event is triggered when any measured panel

currents exceed their respective configured thresholds. These OVL thresholds

can be configured from 1-4000A. Factory default is 800A.

Advertising