Vim1 meter, Alarm and monitoring – GE Industrial Solutions Mini-BDFB User Manual

Page 8

Advertising
background image

Micro-BDCBB ED83368-30

850027449 Issue 1 DRAFT December 2012

8

VIM1 Meter

The VIM1 can be configured to display the voltage, current, and panel identifier of each monitored load bus.

Notes specific to application in this equipment 5067:

1. Lamp Test does not activate 5067 Alarm LED - Figure 1.

Alarm Indication

When an alarm occurs, LCD backlight on the display changes color from green (normal) to red (alarm active). The

front panel text also changes from “No Alarms” to “Alarms”

Navigation Keys

Left and Right Keys are used for menu navigation. Up and Down keys are used to change the parameter values of

the meter. They also allow screen contrast adjustment at:

Menu

►System Parameters►Display Contrast

Figure 8 VIM1 Meter

Alarm and Monitoring

Visual, Audible and Remote Alarms

The VIM1 monitor includes an audible alarm with a user configurable on/off feature. There is a form-C relay for

each of the three alarms for remote monitoring.
All alarms are active when the VIM1 is unpowered. Alarms are asserted when their relay coils are not powered.

Power Loss/Under Voltage

Generates an alarm when power is lost to a load bus or when a user configurable low voltage threshold is reached.

Overload

Generates an alarm when a user configurable current threshold is reached. A configurable time delay may also be

set to avoid nuisance alarms due to bus transients.

Breaker/Fuse

Generates an alarm when either a circuit breaker trips or a fuse blows.

Network Connectivity

There are two RJ45 type connectors on the board for future use.

Previous Menu

Display

Display Menus

Save Changes

Refresh

Arrows Keys

Navigate Menus

Adjust Values in Con