Figure 7 DC Connections


Battery Connections
– Loads - Figure 7

For single load configurations, A and B sections are bridged: Battery, Battery Return, Breaker Loads, and Load

Returns.
1. Connect battery feeds and returns.
2. Connect Breaker loads and returns.

Breakers and Fuse Holders

1. Open Breaker Access Covers by loosening front panel screws.
2. Install protectors and protector holders
3. Close Breaker Access Covers and tighten Breaker Access Screws.
4. Install fuses into fuse holders.
5. Install multi-pole bus kits included with each protector and protector holder occupying 2 or 3 positions.

Load Connections - Figure 7

1. Connect breaker load wires to Breaker Load Connections.
2. Connect breaker load return wires to the Return Bus.

Load A

Battery Connection

Battery Return Connections

Load B

Return Connections

Load A

Return Connections

Load B

Battery Connection

A Breakers

Load Connections

B Breakers

Load Connections

Battery Connections - 3/8” on 1” centers – torque 16 ft-lb

Breaker Load Connections - 1/4” on 5/8” centers – torque 55 in-lb

2-Load configuration shown