Load Overload

Delay

An Overload Delay can be set to prevent nuisance alarms. This delay is

configurable between 0-300 seconds. Factory default is 0 seconds.

Assigned Circuits

The VIM1 has eight individual load circuits with each circuit having voltage and

shunt measurement capability. These circuits are pre-wired with fixed positions

in the Lineage BDFB/BDCBBs. If circuit wiring from the VIM is redressed in the

field this feature can be used to assign the appropriate circuit to the new load

location.

Note: in the 6-load H569-445 circuits 1-6 are attached in a descending order

viewing from the front of the system in a top left to right numbering scheme. The

VIM1 will automatically assign the right circuit if only the first “Load Location” is

utilized and the internal wiring is not touched. Note: if wiring has been

rearranged details of the circuit connections can be seen in T83150-30.

Control and

Operations

Parameters

Description

Start Lamp Test

Cycles the illumination of the front panel LED and Backlight through Red, Amber,

and Green

Clear Latched

Events

Clears a latched Overload Alarm event. Note the Overload Latched Event must be

enabled to have a latched alarm.

Start Alarm Test

Asserts Form-C alarms available at connector J3 in a fixed sequence: Fuse Alarm

(FA), Power Loss (PL), and Overload (OVL). Alarm asserted is displayed on the front

panel. Feature can be used to test the site’s remote monitoring systems and

wiring.

Bullet Style Load Circuit Breakers

Ordering Code

Amperage

CB Positions (Poles)

Min. Wire Gage

407998137

3

1

10

407998145

5

1

10

407998152

10

1

10

407998160

15

1

10

407998178

16

1

10

407998186

20

1

10

407998194

25

1

10

407998202

30

1

10

408213486

40

1

8

407998210

45

1

8

407998228

50

1

6

407998236

60

1

6

407998244

70

1

2

407998251

80

1

2

407998269

90

1

2

407998277

100

1

2

CC848808551

100

2

2

408185353

125

2

2

408185346

150

2

1/0

408564941

200

3

2/0

408573975

225

3

4/0

408535752

250

3

4/0

Multi-Pole Adapter Bus Kits – 1 per multi-pole breaker

Ordering Code

CB Positions (Poles)

Hardware Included

850021775

2

5/16” on 1” centers

850021955

3

5/16” on 1” centers