6 - 2 Off Line Equalization Operation

Issue 4 January 2008

Equalization

Notes

During the equalization process the gassing rate of the batteries will
be dramatically increased. Ensure that adequate ventilation is
provided during this period.

During the equalization process the converter status LEDs should
be as follows:

– On/Standby LED is Green, indicating On.
– Alarm LED is not lit.
– Equalize Current LED is Yellow, indicating current >10A.

As the equalization process proceeds the battery current will
steadily decrease and the Equalize Current LED will go off; this is
normal operation.

At the end of the 12/24-hour period the converter should switch to
standby mode, and LEDs should be as follows:

– On/Standby LED is Yellow, indicating Standby.
– Alarm LED is not lit.
– Equalize Current Yellow LED is flashing, indicating that the

equalization process is complete.

The equalization process will terminate automatically after a period
of time set by the switch on the back of the converter (12/24 hours).