Note that the natural convection condition was
measured at 0.05 m/s to 0.1 m/s (10ft./min. to 20
ft./min.); however, systems in which these power
modules may be used typically generate natural
convection airflow rates of 0.3 m/s (60 ft./min.) due to
other heat dissipating components in the system. The
use of Figures 53 - 59 are shown in the following
example:

Example
What is the minimum airflow necessary for a
JRW060A0F operating at VI = 48 V, an output current
of 42A, and a maximum ambient temperature of 70 °C
in transverse orientation.

Solution:

Given: VI = 48V

Io = 48A

T

A

= 70 °C

Determine airflow (V) (Use Figure 53):

V = 1m/sec. (200ft./min.)

O

UT

P

UT

CURRE

NT

, I

O

(A

)

0

2

4

6

8

10

12

14

16

18

20

20

30

40

50

60

70

80

90

Natural Convection

1.0 m/s (200 ft./min)

2.0 m/s (400 ft./min)

LOCAL AMBIENT TEMPERATURE, T

A

(

°C)

Figure 53. Output Power Derating for JRW017A0B
(Vo = 12V) in Transverse Orientation with no
baseplate; Airflow Direction From Vin(+) to Vin (-);
Vin = 48V.

O

UT

P

UT

CURRE

NT

, I

O

(A

)

0

10

20

30

40

50

60

70

20

30

40

50

60

70

80

90

Natural Convection

1.0 m/s (200 ft./min)

2.0 m/s (400 ft./min)

LOCAL AMBIENT TEMPERATURE, T

A

(

°C)

Figure 55. Output Power Derating for JRW060A0F (Vo
= 3.3V) in Transverse Orientation with no baseplate;
Airflow Direction From Vin(+) to Vin(-); Vin = 48V.

O

UT

P

UT

CURRE

NT

, I

O

(A

)

0

10

20

30

40

50

60

70

20

30

40

50

60

70

80

90

Natural Convection

1.0 m/s (200 ft./min)

2.0 m/s (400 ft./min)

LOCAL AMBIENT TEMPERATURE, T

A

(

°C)

Figure 56. Output Power Derating for JRW065A0G (Vo
= 2.5V) in Transverse Orientation with no baseplate;
Airflow Direction From Vin(+) to Vin(-); Vin = 48V.

O

UT

P

UT

CURRE

NT

, I

O

(A

)

0

10

20

30

40

50

60

70

20

30

40

50

60

70

80

90

Natural Convection

1.0 m/s (200 ft./min)

2.0 m/s (400 ft./min)

LOCAL AMBIENT TEMPERATURE, T

A

(

°C)

Figure 57. Output Power Derating for JRW065A0Y (Vo
= 1.8V) in Transverse Orientation with no baseplate;
Airflow Direction From Vin(+) to Vin(-); Vin = 48V.

O

UT

P

UT

CURRE

NT

, I

O

(A

)

0

5

10

15

20

25

30

35

40

45

50

20

30

40

50

60

70

80

90

Natural Convection

1.0 m/s (200 ft./min)

2.0 m/s (400 ft./min)

LOCAL AMBIENT TEMPERATURE, T

A

(

°C)

Figure 54. Output Power Derating for JRW040A0A
(Vo = 5V) in Transverse Orientation with no
baseplate; Airflow Direction From Vin(+) to Vin (-);
Vin = 48V.