Bell & Gossett HT 202A SM Models CHXS Fixed Tube Sheet Heat Exchangers User Manual

Page 2

Advertising
background image

12. Location of the operating fluids in the heat exchanger can be

a function of the application. A few tips for the location of the

operating fluids are:
a. As a cooler, the preferred arrangement is with the hot medi-

um through the shell and the cooling medium through the

tubes. When the hot fluid is dirty or fouling, it is better to put

it through the tubes because they are easier to clean. With

single pass units be sure the shell inlet is on the same end

as the tube side outlet. In two pass units, the shell inlet

should be at the inlet-outlet bonnet end. It is customary for

the cooling medium to enter the lower bonnet connection,

although this can be reversed if necessary.

b. As a heater, the hot medium, usually steam or hot water,

must be in the shell. If it is steam, either of the shell con-

nections, or both, can be used, dependent on the actual

entering velocities.

c. For the above applications and for temperatures above

150°F, the higher temperature fluid should be circulated

through the shell side of the exchanger and precaution

should be taken to avoid shock from abrupt changes in

fluid circulation temperatures.

13. Steam hammer can cause serious damage to the tubes of any

heat exchanger. A careful consideration of the following points

before an installation is made can prevent costly repairs which

may be caused by steam hammer.
a. A vacuum breaker and/or vent, should be used in accord-

ance with the type of steam system installed.

b. The proper trap for the steam system installed should be

used.

c. The trap and the condensate return line to the trap should

be properly sized for the total capacity of the convertor.

d. The trap should be sized for the pressure at the trap, not

the inlet pressure to the steam controller.

e. The trap must drain into an unpressurized condensate re-

turn system. Condensate return lines must not be run at an

elevation above the bottom of the heat exchanger. To do so

may result in a buildup of the condensate level in the heat

exchanger, which could cause water hammer and damaged

tubes.

CAUTION: During times of shutdown, volumetric

expansion can occur. We recommend the installation

of a properly sized relief valve on both sides of the heat

exchanger.

OPERATION

1. When placing a unit in operation, open the vent connections

and start to circulate the cold medium only. Be sure that the

passages in the exchanger are entirely filled with the cold fluid

before closing the vents. The hot medium should then be intro-

duced gradually until all passages are filled with liquid, close

vents and slowly bring the unit up to temperature.

2. Start operation gradually. Do not admit hot fluid to the unit

suddenly when empty or cold. Do not shock unit with cold fluid

when unit is hot.

CAUTION: Fluids must be gradually introduced to the

unit. Failure to do so can cause damage to the heat

exchanger.

INSTALLATION

1

1. Before installing this equipment, environment and service

conditions should be checked for compatibility with materials

of construction. Contact your nearest Bell & Gossett

Representative if you are not sure what the actual materials of

construction are.

1

2. Provide valves and by-passes in the piping system so that

both the shell and tube sides may be by-passed to permit

inspection or repair.

1

3. Provide thermometer well and pressure gauge connections in

all piping to and from the unit and locate as near the unit as

possible.

1

4. Provide convenient means for frequently cleaning the unit as

suggested under “Maintenance.”

1

5. Provide necessary air vent cocks for units so they can be

purged to prevent or relieve vapor or gas binding of either the

tube or the shell sides.

1

6. Foundations must be adequate so that exchangers will not

settle and cause piping strains. Foundation bolts should be

set to allow for setting inaccuracies. In concrete footings, pipe

sleeves at least one size larger than bolt diameter slipped over

the bolt and cast in place are best for this purpose, as they

allow the bolt center to be adjusted after the foundation has

set.

1

7. Loosen foundation bolts at one end of unit to allow free

expansion of shells. Oval holes in foundation brackets are

provided for this purpose.

1

8. Set exchangers level and square so that pipe connections

may be made without forcing.

1

9. Inspect all openings in exchanger for foreign material. Re-

move all thread protectors and shipping pads just before

installing. Do not expose units to the elements with pads or

other covers removed from openings since rain water may

enter the unit and cause severe damage due to freezing.

10. Be sure the entire system is clean before starting operation to

prevent plugging of tubes with sand or refuse. The use of

strainers in settling tanks in pipe lines leading to the unit is

recommended.

11. Drain connections should not be piped to a common closed

manifold.

2

Advertising
This manual is related to the following products: