John Wood Envirosense Power Vent User Manual

Page 13

Advertising
background image

13

Figure 10 shows typical attachment of water piping to the water heater.

The water heater is equipped with 3/4 inch NPT water connections.

note: If using copper tubing, solder tubing to an adapter before

attaching the adapter to the water heater connections. do not

solder the water lines directly to the water heater connections.

It will harm the dip tube and damage the tank.

T & P Valve and Pipe Insulation (if supplied)

Remove insulation for T & P valve and pipe connections from carton.

fIGure 11.

Fit pipe insulation over the incoming cold water line and the hot water

line. Make sure that the insulation is against the top cover of the heater.

Fit T & P valve insulation over valve. Make sure that the insulation

does not interfere with the lever of the T & P valve.

Secure all insulation using tape.

teMperature-pressure relIef valve

This heater is provided with a properly certified combination

temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment of
materials as meeting requirements for Relief Valves for Hot Water Supply
Systems, ANSI Z21.22 • CSA 4.4, and code requirements of ASME.

If replaced, the valve must meet the requirements of local codes, but

not less than a combination temperature and pressure relief valve

certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to

exceed the marked hydrostatic working pressure of the water heater

(150 psi = 1,035 kPa) and a discharge capacity not less than the water

heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be

removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into

the fitting of the water heater designed for the relief valve. Position

the valve downward and provide tubing so that any discharge will

exit only within 6 inches (15.2 cm) above, or at any distance below

the structural floor. Be certain that no contact is made with any live

electrical part. The discharge opening must not be blocked or reduced

in size under any circumstances. Excessive length, over 30 feet (9.14

m), or use of more than four elbows can cause restriction and reduce

the discharge capacity of the valve, see Figures 10 or 14.

No valve or other obstruction is to be placed between the relief valve

and the tank. Do not connect tubing directly to discharge drain unless

a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to

life, or property damage, the relief valve must be allowed to discharge

water in quantities should circumstances demand. If the discharge

pipe is not connected to a drain or other suitable means, the water

flow may cause property damage.

The Discharge Pipe:

• Should not be smaller in size than the outlet pipe size of the valve, or

have any reducing couplings or other restrictions.

• Should not be plugged or blocked.
• Should be of material listed for hot water distribution.
• Should be installed so as to allow complete drainage of both the

temperature-pressure relief valve, and the discharge pipe.

• Must terminate a maximum of six inches above a floor drain or external

to the building. In cold climates, it is recommended that the discharge

pipe be terminated at an adequate drain inside the building.

• Should not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually operated

periodically. Caution should be taken to ensure that (1) no one is in front

of or around the outlet of the temperature-pressure relief valve discharge

line, and (2) the water manually discharged will not cause any bodily injury

or property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset and

continues to release water, immediately close the cold water inlet

to the water heater, follow the draining instructions, and replace the

temperature-pressure relief valve with a new one.

Advertising