John Wood Envirosense Power Vent User Manual

Page 17

Advertising
background image

17

plannInG the vent sYsteM

If the water heater is being installed as a replacement for an existing

power vented heater in pre-existing venting, a thorough inspection

of the existing venting system must be performed prior to any

installation work. Verify that the correct material as detailed above

has been used, and that the minimum or maximum vent lengths and

terminal location as detailed in this manual have been met. Carefully

inspect the entire venting system for any signs of cracks or fractures,

particularly at the joints between elbows and other fittings and the

straight runs of vent pipe. Check the system for signs of sagging

or other stresses in the joints as a result of misalignment of any

components in the system. If any of these conditions are found, they

must be corrected in accordance with the venting instructions in this

manual before completing the installation and putting the water

heater into service.

Installation of this water heater must comply with CAN/CSA B149.1

- Natural Gas and Propane Installation Code which requires the vent

system components be certified to ULC S636.

This water heater has been design certified to be vented with PVC

pipe certified and marked as complying with ULC S636. This water heater

is supplied with a 2 inch 22.5 degree termination elbow that is a special

fitting that must be used with this appliance. Any outlet piping, fittings and

glue used to vent this appliance that is not supplied by the manufacturer

must comply with the ULC S636 requirements.
For water heaters in locations with high ambient temperatures (above

100°F) it is recommended that CPVC pipe and fittings be used. A

22.5 degree elbow (2” vent pipe) or a 45 degree elbow (3” and 4”

vent pipe) with an installed screen VENT TERMINAL must be used

in all cases.
Plan the route of the vent system from the discharge of the blower

to the planned location of the vent terminal.
1. Layout total vent system to use a minimum of vent pipe and elbows.
2. This water heater is capable of venting flue gases equivalent to

25’ (7.6 m) of 2” pipe, 65’ (19.8 m) of 3” pipe, or 128’ (39.0 m) of

4” pipe as listed in Table 1.

taBle 1

Number of

2” Maximum

3” Maximum

4” Maximum

90° Elbows Pipe - ft. (m)

Pipe - ft. (m)

Pipe - ft. (m)

1

20 (6.1)

60 (18.3)

120 (36.6)

2

15 (4.6)

55 (16.8)

112 (34.1)

3

10 (3.0)

50 (15.2)

104 (31.7)

4

--

45 (13.7)

96 (29.3)

5

--

40 (12.2)

88 (26.8)

6

--

35 (10.7)

80 (24.3)

The minimum vent lengths for each of the pipe sizes is one 90° on top of

the unit plus 2’ (61 cm) of straight pipe and the appropriate termination.

note: The equivalent feet (m) of pipe listed above are exclusive of

the termination. That is, the termination, with an installed screen, is

assumed to be in the system and the remainder of the system

must not exceed the lengths discussed above.

3. The blower discharge adapter is made to accept only straight

sections of 2” pipe. To start, a minimum of 2 inches (5.1 cm) of 2”

pipe must be attached to the blower discharge, see Figure 17.

If using 2” inch vent pipe:

A minimum of 2 inches (5.1 cm) must be attached to the blower

before the first elbow. After the first elbow add the additional

venting required for the installation. The total system cannot

exceed the lengths discussed above, where each elbow is equal

to 5 feet (1.5 m) of straight pipe.

If using 3” or 4” inch vent pipe:

Two inches (5.1 cm) of pipe must be attached to the blower

discharge before adding a reducer to acquire the desired pipe

diameter. An appropriately sized 45 degree elbow (supplied

locally-a schedule 40 DWV) vent terminal must be obtained

with an equivalent screen (supplied in vent kit). The total system

cannot exceed the equivalent pipe lengths discussed above

where each elbow is equal to 5 feet (1.5 m) of straight pipe (3”

vent pipe) or 8 feet (2.4 m) of straight pipe (4” vent pipe).

4. There will be some installations where condensate will be formed

in the horizontal runs of the vent system. This condensate will

run into the condensate boot attached to the blower and out the

fitting. The water heater is shipped with condensate hose that

attaches to the fitting on the condensate boot. No other Tee or

fitting is required. See Figures 17, 20 and 21.

condensate

This water heater is a condensing unit and requires a drain to be

located in close proximity to allow the condensate to drain safely.

The condensate drains from the unit at the exhaust tee located at the

bottom of the unit (see figure 16) and from two places on the blower

assembly (see figure 17). Condensate from this water heater is mildly

acidic. Please note that some local codes require that condensate is

treated by using a pH neutralizing filter prior to disposal.
NOTE: It is important that the condensate hose on the bottom of the unit

is not installed elevated above the clamp that is secured to the side of the

jacket, see figure 16. This must be true for the entire length of the hose

from the clamp to the exit into an appropriate drain. If these instructions

are not followed or if the condensate hose is blocked, water will spill from

the condensate trap. As with every water heater installation, a metal

drain pan should be used to prevent water damage to the surrounding

area. If necessary, a condensate pump with an incorporated reservoir

may be used to pump the water to an appropriate drain. To avoid

condensate spillage, select a pump with an overflow switch.
Caution must be used to ensure that the drain is free and clear of debris

and will not allow backflow through the condensate hose. Consideration

must be given to avoid freezing of the condensate lines which could result

in excessive build up of condensate inside the water heater. Waterproof

heat tape may be required to prevent freezing of the condensate lines.

Please ensure that the outlet of the condensate drain does not create

a slippery condition which could lead to personal injury.

Advertising