John Wood Envirosense Power Vent User Manual

Page 29

Advertising
background image

29

INSTALLED IN SUITABLE AREA: To insure sufficient ventilation

and combustion air supply, proper clearances from the water heater

must be maintained. See “Locating the New Water Heater” section.

Combustible materials such as clothing, cleaning materials, or

flammable liquids, etc. must not be placed against or adjacent to

the water heater which can cause a fire.

anode rod InspectIon

Each water heater contains at least one anode rod, which will slowly

deplete (due to electrolysis) prolonging the life of the water heater by

protecting the glass-lined tank from corrosion. Adverse water quality,

hotter water temperatures, high hot water usage, and water softening

methods can increase the rate of anode rod depletion. Once the anode rod

is depleted, the tank will start to corrode, eventually developing a leak.
Certain water conditions will cause a reaction between the anode rod

and the water. The most common complaint associated with the anode

rod is a “rotten egg smell” produced from the presence of hydrogen

sulfide gas dissolved in the water. IMPORTANT: Do not remove this

rod permanently as it will void any warranties. The parts list includes a

special anode rod that can be ordered if water odor or discoloration occurs.

NOTE: This rod may reduce but not eliminate water odor problems. The

water supply system may require special filtration equipment from a water

conditioning company to successfully eliminate all water odor problems.
Artificially softened water is exceedingly corrosive because the

process substitutes sodium ions for magnesium and calcium ions.

The use of a water softener may decrease the life of the water

heater tank.
The anode rod should be removed from the water heater tank every

3 years for inspection. NOTE: artificially softened water requires the

anode rod to be inspected annually.
The following are typical (but not all) signs of a depleted anode rod:

* The majority of the rods diameter is less than 3/8”.

* Significant sections of the support wire (approx. 1/3 or more of the

anode rod’s length) are visible.

If the anode rod show signs of either or both it should be replaced.
NOTE: Whether re-installing or replacing the anode rod, check for

any leaks and immediately correct if found.
In replacing the anode:
1. Turn off gas supply to the water heater.

2. Shut off the water supply and open a nearby hot water faucet to

depressurize the water tank.

3. Drain approximately 5 gallons of water from tank (Refer to “Draining

and Flushing” for proper procedures). Close drain valve.

4. Remove old anode rod.

5. Use Teflon® tape or approved pipe sealant on threads and install

new anode rod.

6. Turn on water supply and open nearby hot water faucet to purge air

from water system. Check for any leaks and immediately correct

any if found.
Restart the water heater as directed under “Operating Your Water

Heater.” See the Repair Parts Illustration for anode rod location.

fIGure a. anode rod depletIon.

teMperature-pressure relIef valve operatIon

The temperature-pressure relief valve must be manually operated

at least once a year.

fIGure 22.

When checking the temperature-pressure relief valve operation,

make sure that (1) no one is in front of or around the outlet of

the temperature-pressure relief valve discharge line, and (2) that

the water discharge will not cause any property damage, as the

water may be extremely hot, see Figure 22.
If after manually operating the valve, it fails to completely reset

and continues to release water, immediately close the cold water

inlet to the water heater, follow the draining instructions, and

replace the temperature-pressure relief valve with a new one.
If the temperature-pressure relief valve on the appliance weeps

or discharges periodically, this may be due to thermal expansion.

You may have a check valve installed in the water line or a water

meter with a check valve. Consult your local water supplier

or service agency for further information. Do not plug the

temperature-pressure relief valve.

draInInG and flushInG

It is recommended that the tank be drained and flushed every 6

months to remove sediment which may build up during operation.

the water heater should be drained if being shut down during freezing

temperatures. To drain the tank, perform the following steps:

1. Set the blower switch to the “OFF” position.

2. Open a nearby hot water faucet until the water is no longer hot.

3. Close the cold water inlet valve.

4. Connect a hose to drain valve and terminate to an adequate

drain or external to the building.

5. OPEN water heater drain valve and allow all of the water to drain

from tank. Flush tank with water as needed to remove sediment.

6. CLOSE the drain valve, refill the tank, and restart the heater as

directed in this manual.

7. If the water heater is going to be shut down for an extended

period, the drain valve should be left open.

8. IMPORTANT: Condensation may occur when refilling the tank

and should not be confused with a tank leak.

Advertising