John Wood Envirosense Power Direct Vent (prior to May 2010) User Manual

Page 20

Advertising
background image

20

InstallatIon sequence

cautIon

vent terMInals supplIed wIth heater Must Be used.

NOTE: BEFORE BEGINNING INSTALLATION OF ANY

VENT PIPE READ THE VENT PIPE MANUFACTURER’S

INSTALLATION INSTRUCTIONS.

1. After the points of termination have been determined,

use the cover plates as templates to mark the holes for

the vent pipes to be inserted through the wall. BEWARE OF

CONCEALED WIRING AND PIPING INSIDE OF WALL. If the

vent terminals are being installed on the outside of a finished

wall, it may be easier to mark both the inside and outside

wall. Align the holesby drilling a hole through the center of the

template from the inside through to the outside. The template

can now be positioned on the outside wall using the drilled holes

as a centering point for the template.

A.) MASONRY SIDE WALLS Chisel an opening approximately

1/2” (1.3 cm) larger than the marked circle.

B.) WOODEN SIDE WALLS Drill a pilot hole approximately

one quarter inch outside of the marked circle. This

pilot hole is used as a starting point for a saws-all or

sabre saw blade. Cut around the marked circle staying

approximately one quarter inch outside of the line.

(This will allow the vent pipe to easily slide through

the opening. The resulting gap will be covered by the

vent terminal cover plates.) Repeat this step on the

inside wall if necessary.

2. Cut a length of 3” PVC pipe about 3.5” (8.9 cm) longer than the

wall thickness at the opening.

3. Glue the intake vent terminal to the section of the pipe.

4. Slide the wall plate over pipe to stop against intake vent terminal.

5. Place a bead of caulking (not supplied) around the gap between

the pipe and the wall. Place some of the caulking on the

back of the plate to hold it against the wall after installation.

6. If the vent pipe is installed up to the wall, with a coupling on the

end against the wall opening, the pipe with the vent terminal can

be prepared for gluing before inserting through the wall. Slide the

pipe through the wall and insert into coupling on the other side of

the wall, making sure that the vent terminal ends up pointed in the

correct position (Figure 18 and 19).

fIGure 18.

fIGure 19.

vertIcal vent terMInal InstallatIon

IMportant

when terMInatInG throuGh a roof, the followInG

specIfIcatIons pertaInInG to terMInal locatIon

Must Be followed.

1. Proper support must be provided for all pipe protruding through

the roof.

2. The vertical roof terminals should be sealed with a plumbing

roof boot or equivalent flashing.

3. The intake vent terminals and the exhaust vent terminals must

penetrate the same side of roof.

4. The center line of the intake vent terminal and the center

line of the exhaust vent terminal must be no closer

than 24” (61cm).

5. The intake vent terminal and the exhaust vent terminal must be

oriented facing downward and the same direction.

The specifications are displayed in Figures 20 & 21.

NOTE: Exhaust vent terminal is installed using the same

procedure.

fIGure 20.

fIGure 21.

Advertising