rough-In-dimensions

Model

Units

A

B

C

D

E

F

100

Inches 68.50

49.25

22.00

15.75

3.00

8.00

cm

174

125.09 55.88

40.00

7.62

20.32

top/side Inlet and outlet: 3/4” npt

Gas Inlet: 1/2” npt

capacity, Gas and electrical characteristics

Model

Approximate Capacity

Manifold Pressure

Electrical Characteristics

U.S. Gals.

Liters Gas Type

“WC

kPA

Volts/Hz

Amperes

100

50

189

Nat./LP

0”

0”

120/60

<5

all models - Maximum supply pressure: 14 inches w.c. (3.48kpa)

Minimum supply pressure for natural Gas: 3.50” (.87kpa)

Minimum supply pressure for propane Gas: 8.00” (1.99kpa)

Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.

recovery capacities - u.s. Gallons/hr. and liters/hr. at temperature rise Indicated

Model

Input

Recovery Capacities

Rating

(Btu/hr)

Rating

(kW)

Temp.

Rise

F

30

40

50

60

70

80

90

100

110

120

130

140

C

17

22

28

33

39

44

50

56

61

67

72

78

100

100,000

29.3

GPH

387

291

233

194

166

145

129

116

106

97

90

83

LPH

1465

1102

882

734

628

549

488

439

401

367

341

314

Recovery capacity based on 96% thermal efficiency

InstallatIon consIderatIons

rouGh In dIMensIons

fIGure 1a.