Vent Terminal Installation Precautions

Note the following vent terminal installation requirements

• Do not install the vent terminal indoors

• Install the vent terminal with a downward slope

upward

slope

downward

slope

• Avoid storing hazardous

objects near the terminal

Gasoline

Gas

Vent terminal

Vent terminal

Snow
drift

Tree

• Avoid installing the terminal where obstacles

will block it

Do not install the vent terminals vertically in-line. Do not cover
the vent terminal with any type of protective screen or enclosure.
In-line or blocked terminals can cause abnormal combustion
resulting in undesired performance from the water heater.

Vertical position not allowed.

8.

Vent Pipe Installation

• This appliance requires the use of special concentric type vent pipe specified by Noritz America.

Do not attempt to use materials that are not specified for use on this appliance.

WARNING

Be sure to do

CARBON MONOXIDE POISONING
Follow all vent system requirements in accordance with relevant local or state regulation,
or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI
Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with NSCNGPI.

> 75mm (3")

(0.8"-3")

20-75mm

< 20mm

(0.8")

• Install with the proper length protruding through the wall

Proper installation.
The red line can be
seen, but not more
than 55mm (2.2")
from the wall.

not far
enough

too far

• Clearance from vent terminal.
If multiple units are installed, terminals must be separated

by 300mm (12") or more in a plain view regardless of the
vertical clearance.

Vent terminal

Vent terminal

300mm (12") or more

300mm (12") or more