Installation clearances, Warning – John Wood Noritz Concentric Vent - NR98-DVC (N-0751M) User Manual

Page 7

Advertising
background image

7

6.

Installation Clearances

Before installing, check for the following:

Install in accordance with relevant building and mechanical codes, as well as any local, state or
national regulations, or in the absence of local and state codes, to the National Fuel Gas Code ANSI
Z223.1/NFPA 54 – latest edition. In Canada, see NSCNGPIC for detailed requirements.

WARNING

Item

Distance from combustibles

• Maintain the following clearances

from both combustible and
non-combustible materials.

• There must be a clearance of 600mm

(24") or more in front of the Flue terminal.

• This restriction will not be applied to an

area where an effective shield makes a
clearance of 600mm (24") or more in
front of the exhaust outlet.

Check

Illustration

• If possible, leave 200mm (8") or more on

either side of the unit to facilitate inspection.

• If possible, leave 600mm (24") or more

in front of the unit to facilitate maintenance
and service if necessary.

• If possible, leave 75mm (3") or more

above and below the vent pipe to facilitate
inspection and repair if necessary.

Securing of space for

repair/inspection

600mm
(24") or
more

200mm

(8") or

more

Outdoor Clearances to Opening

into Any Building

Distance from
the side

300mm (12")

or more

50mm (2")

or more

There must be no
building opening
within this area.

300mm (12")
or more

Flue terminal

300mm (12")
or more

300mm

(12") or

more

300mm

(12") or

more

100mm (4")

or more

75mm (3") or more

75mm (3") or more

200mm

(8") or

more