Vent Clearances When Heater is In-

stalled Indoors

• 4' below, 4' horizontally from, or 1' above

any door, operable window, or gravity air
inlet into any building.
3' above any forced air inlet within 10'.

Maintain the following clearances to any

opening in any building:

Illustration

(Noritz vent cap)

• 1' below, 1' horizontally from, or 1' above

any door, operable window, or gravity air
inlet into any building.
3' above any forced air inlet within 10'.

Vent Clearances When Heater is In-

stalled Outdoors With a Vent Cap

* All clearance requirements are in accordance with ANSI Z21.10.3a-2003 and the National Fuel Gas

Code, ANSI Z223.1.

* For Installations in Canada, clearances are as follows: To windows, doors, & gravity air inlets: 36".

To forced air inlets: 6'. These clearance requirements hold true for all of the above situations: Indoor,

Outdoor w/vent cap, & Recess Box.

3’

1’

4’

4’

3’

1’

1’

1’

Clearance Requirements from Vent Terminations to Building Openings

• 1' below, 1' horizontally from, or 1' above

any door, operable window, or gravity air

inlet into any building.

3' above any forced air inlet within 10'.

Vent Clearances When Heater is

Installed in a Recess Box

(recess box installation with cover removed)

3'

1'

1'

1'