Combustion air – John Wood Noritz N-069M_N-069S User Manual

Page 47

Advertising
background image

47

• Provide two permanent openings to allow

circulation of combustion air.

• Make each opening 194 square inches if they

provide indoor air, and 100 square inches for
outdoor air.

• If the unit is installed in a mechanical closet,

provide a 24" clearance in front of the unit to
the door.

• If combustion air will be provided through a

duct, size the duct to provide 60 cubic feet of
fresh air per minute.

Supply combustion air to the units as per the National Fuel Gas Code, ANSI Z223.1.

Combustion Air

Openings supplying indoor air

20"

10"

20"

10"