John Wood Noritz N-069M_N-069S User Manual

Page 46

Advertising
background image

46

Vertical Vent Termination

Appliance

Adapter

Firestop

Firestop/

Support

Roof

Flashing

Rain

Cap

Hanger

Strap

Elbow

Condensation

Drain (Install

According to

Local Codes)

3'

Max.

• Terminate at least 6' from the

combustion air intake of any
appliance, and 3' from any
other building opening, gas
utility meter, service regulator
etc.

• Enclose exterior vent systems

below the roof line to limit
condensation and protect
against mechanical failure.

• When the vent penetrates a

floor or ceiling and is not
running in a fire rated shaft, a
firestop and support is required.

• Terminate the vent system at

least 3' above, but not more
than 6' above the roof line, or
according to the vent pipe
manufacturer's instructions.

• Provide vertical support every

12' or as required by the vent
pipe manufacturer's instructions.

• Slope the horizontal vent 1/4"

downwards for every 12".

• Do not vent straight upwards.

Always have a horizontal section
of venting.

• Install a condensation drain in

the horizontal section of the
venting.

Advertising