Technical data venting, table 3 – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 10

Advertising
background image

10

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting mutiple tank type heaters using Type B

vent pipe, follow the installation diagram (figure 8) and

tables below which give sizing and data based upon

NFPA 54/ANSI Z223.

TECHNICAL DATA VENTING, TABLE 3

MODEL JWSM71120

Input: 120,000 Btuh Total Vent Height (Feet)

Draft Hood: 5”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (inches)

120,000

1 Ft.

7

7

7

6

6

6

6

6

120,000

2 Ft.

6

6

6

6

6

6

6

5

123,000

3 Ft.

6

6

6

6

6

5

5

5

Number of Heaters

Combined Input in

Thousands of Btuh

Manifold and Common Vent Diameter (In inches)

2

3

4

240

10

8

8

7

7

7

6

7

360

10

10

10

10

8

8

7

7

480

12

12

12

10

10

10

8

8

MODEL JWSM95199, JWSM76199, & (A)JWSM100199
Input: 199,000 Btuh
Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

199,000

-

-

8

8

8

8

8

7

199,000

8

8

8

8

7

7

7

7

190,000

8

7

7

7

7

7

6

6

197,000

8

7

7

7

7

7

7

6

199,000

8

8

7

7

7

7

7

6

Number of Heaters

Combined Input in

Thousands of Btuh

Manifold & Common Vent Diameter

2

358

10

10

10

10

8

8

7

7

380

12

10

10

10

10

8

7

7

394/398

12

10

10

10

10

8

8

7

3

537

14

12

12

12

10

10

10

8

570

14

12

12

12

10

10

10

10

591/597

14

14

12

12

12

10

10

10

4

716

14

14

14

12

12

12

10

10

760

16

14

14

14

12

12

10

10

788/796

16

14

14

14

12

12

12

10